The following table shows TCP/UDP port numbers used by the built-in EtherNet/IP port, whether or not it is reserved by the system, whether or not the port number can be changed by the user, protocol used, default state, usage, and how to close the port from the default open state, for each application.
TCP/UDP ports (servers) other than those shown below are not used. For more information please see the CPU Unit Built-in Ethernet/IP Port user manual (W506).

Application CPU Unit Model UDP port TCP Port System Reserved Port Number Change Protocol used Default Usage How to close the port from open state
FTP Server All models --- 20 Reserved Not Possible FTP Closed Used when using the FTP server ---
--- 21 --- Not Possible Closed ---
SSH/SFTP All models --- 22 Reserved Not Possible SSH/SFTP Closed For maintenance ---
DNS client All models 53 --- Reserved Not Possible DNS Closed Used when using the DNS client ---
BOOTP client All models 68 --- Reserved Not Possible BOOTP Closed Used when using the BOOTP client ---
HTTP server All models 80 --- Reserved Not Possible
HTTP Closed(Post v1.50) Used for communications with
Sysmac Studio pre v1.50 or when DIP switches set
---
NTP client All models 123 --- --- Possible NTP Closed Used when using the NTP client. ---
Application CPU Unit Model UDP port TCP Port System Reserved Port Number Change Protocol used Default Usage How to close the port from open state
SNMP All models 161 --- --- Possible SNMP (SNMPv1, SNMPv2C Closed Used when using the SNMP agent ---
SNMP trap All models 162 --- --- Possible Closed Used when using the SNMP trap ---
HTPPS server All models --- 443 Reserved Not Possible HTTPS Open Used for communications with
Sysmac Studio post 1.50
Make one of the following settings.

Use the Packet Filter. *1

Set the DIP switch to Enable connections to the Sysmac Studio and NA that are not supporting secure communication.

Ethernet/IP tag data links
All models
2222
---
Reserved
Not Possible
CIP
Open
Used for Ethernet/IP tag data links
Set Built-in EtherNet/IP Port Settings - CIP Settings - CIP Message Server to Do not use on Sysmac Studio.
All NJ series models
2223
---
Reserved
Not Possible
Open
Application
CPU Unit Model
UDP Port
TCP Port
System Reserved
Port Number Change
Protocol used
Default
Usage
How to close the port from the open state
FINS/UDP
All NJ-series
models
All NX1P2
NX102*2
NX701-1▢20*2
9600
---
---
Possible
FINS (Omron protocol)
Open
Used for FINS/UDP
Set Built-in EtherNet/IP Port Settings - FINS
Settings - FINS/UDP to Do not use
on the Sysmac Studio.
FINS/TCP
All NJ-series
models
All NX102*2
NX701-1▢20*2
---
9600
---
Possible
Open
Used for FINS TCP
Set Built-in EtherNet/IP Port Settings - FINS
Settings - FINS/UDP to Do not use
on the Sysmac Studio.
Sysmac Studio
All models
9600
---
Reserved
Not Possible
Open
Used for communication with Sysmac Studio
Use the Packet Filter *1
CPU Units that support USB Port
All NJ-series
models
All NX701*3
2224
---
Reserved
Not Possible
Closed*4
---
Application
CPU Unit Model
UDP Port
TCP Port
System Reserved
Port Number Change
Protocol used
Default
Usage
How to close the port from the open state
Maintenance
All models
---
9610
Reserved
Not Possible
TCP (Omron protocol)
Closed
For maintenance
---
CIP messages
All models
44818
44818
Reserved
Not Possible
CIP
Open
Used for CIP messages
Set Built-in EtherNet/IP Port Settings - CIP Settings - CIP Message Server to Do not use on Sysmac Studio.
OPC UA
CPU Units that
support OPC UA
NJ501-1▢00
NX102-▢▢▢▢*5
NX701-1▢▢▢*5


---
4840
---
Possible
OPC UA
Closed
Used for OPC UA
---
TCP/UDP message service
CPU Units that
support TCP/UDP message service
NX102-▢▢▢▢
64000
64000
---
Possible
TCP/UDP
Closed
Used when using the TCP/UDP message service
---
Application
CPU Unit model
UDP port
TCP port
System reserved
Port number change
Protocol used
Default
Usage
How to close the port from the open state
SECS/GEM connection service
CPU Units that
support SECS/
GEM
NJ501-1340
---
9700
Reserved
Not Possible
TCP.UDP (Omron Protocol)
Open
Used when using the SECS/GEM connection service. Use the Packet Filter
---
5000
---
Possible
SECS-II
Closed
---
DB connection service
CPU Units that support DB connection
NJ501-XX20
NJ101-▢▢20
NX102-▢▢20
NX701-1▢20


---
9800
Reserved
Not Possible
TCP (Omron Protocol)
Open
Used when using the DB connection service.
Use the Packet Filter
---
9801
Open
---
9810
Open
---
9811
Open
Application
CPU Unit model
UDP port
TCP port
System reserved
Port number change
Protocol used
Default
Usage
How to close the port from an open state
Robot Integration
CPU Units that
support Robot Integrated Controller
NJ501-R▢▢▢
1989
---
Reserved
Not Possible
UDP (Omron Protocol)
Open
Used for communications with ACE (including Application Manager) or Sysmac Studio.
Use the Packet Filter.

To close the ports on the left at once, remove the SD Memory Card, execute clear all memory operation, then restart the Controller.
1992
---
Open
1997
1997
TCP/UDP (Omron Protocol)
Open
Open
65533
---
UDP (Omron Protocol)
Open
65534
---
Open
1990
---
Closed
1993
---
Closed
69
---
TFTP
Closed
---
43234
TCP (Omron Protocol)
Closed
---
48987
Closed

*1. Closing the port may prevent communications with the Sysmac Studio. Refer to Troubleshooting When You Cannot Go Online from the Sysmac Studio in the NJ/NX-series Troubleshooting Manual (Cat. No. W503) on how to make corrections.
*2. This port number is supported only on Port 2. It cannot be used on Port 1.
*3. Only if the CPU unit has USB port.
*4. Always closed for the built-in EtherNet/IP port. Opened for the USB port only.